Home Insulation Products HVAC&R Accesories Contact us
Search Products
Insulation Product  

 

AEROFLEX-HF
Specification
size & packing
 
 
 
 
 
 


...

 
AVERAGE PHYSICAL
PROPERTIES
AEROFLEX - HF TEST METHODS
INSULATION
Cell Structure Closed cell -
Density lb/ft.³ (gm/cm³) 3.0-5.0 ASTM D 1667
(0.048~0.080)
Thermal Conductivity 32°F 0.24 ASTM D 177
JIS A 1412-1989
DIN 52613
BTU.in/ft.² hr. °F (W/mK) mean temp (0.035)
104°F(40 °C) 0.27
mean temp (0.040)
Service Themperature -76 °F to 250 °F can be applicable
-200 °C to 125°C down to -200°C
Water Vapor Permeability (perm-in) >#-0.15 perm-in. ASTM C355
u>#- 4,000 DIN 52615
Water Absorption (% by weight) 5 ASTM D 1056
Ozone Resistance Excellent ASTM D 1171
Thermal Stability 7 days200°F 5 ASTM C 534
(% shrinkage) 7 days220°F 6
Flammability & Smoke Developed Self-extinguishing ASTM D 635
Class V 0 UL - 94
Class 5.3 EMPA *
Non-Flammable JIS K 6911
B-2 DIN 4102
Weather and Ultraviolet Resistance Good -
Stainless steel & Copper Corrosion Negligible -
Nitrosamines Content Non-Negligible US-FDA
Flexibility at Low Temperature Excellent -
Elongation Excellent -
Specification Compliance : ASTM 534-88
* EMPA : Swiss Fedral Laboratories for Materials Testing and Research.

 

  
 
 

 

 

© 2000 Eastern Polymer Group. All rights reserved.
Aeroflex International Co.,Ltd.
770 Moo 6 Teperak Road, Amphure Muang, Samutprakan 10270, Thailand.
Tel:(662) 383-6599 (15 lines) Fax:(662) 383-6533,