Home Insulation Products HVAC&R Accesories Contact us

 

AEROFLEX
Introduction
Application
Characteristics
Hot Water Piping
Chilled Water Piping
Ducting System
Size Chart&Packing
Quality Control
Specifications
Technical Information


 
Properties Aeroflex-Standard Test Method
Cell Structure Closed Cell -
Density  lbs/ft3 (Kg/m3) 2.5-5.0 (40-80)* ASTM D 1667
Thermal Conductivity Mean Temp -4oF 32oF 75oF 90oF 104oF ASTM C 177
BTU.in/ft2 hr oF  (-20oC) (0oC) (24oC) (32oC) (40oC) ASTM C 518
(W/ m.K) K-Value 0.215 0.23 0.247 0.256 0.259 JIS A 1412
  (0.0310) (0.0330) (0.0356) (0.0365) (0.0374) EN ISO 8497
Service Temperature -70 oF to 257 oF Becomes hard at -57oC but can be used even at -200oC
-57 oC to 125 oC
Water Absorption  < 10 (% by weight) ASTM D 1056
< 0.20 (% by volume) ASTM C 209
Water Vapor Permeability  < 0.10 (1.44 x 10-10 g/Pa.s.m) ASTM E 96
perm.in (g/Pa.s.m)
Ozone Resistance Very Good ASTM D 1149  
ASTM D 1171
UV Weather Resistance Very Good ASTM G 154
Heat Stability (%Shrinkage) < 7% ASTM C 534
@ 220oF (104oC) x 7 days
Flammability & Smoke Density Class V-0 UL 94
25/50 ASTM E 84
Self-Extinguishing ASTM D 635
Class 5.3 EMPA (Switzerland)
Non-Flammable JIS K 6911
Pass IMO
Mold Resistance   Meet Requirement (Rating 1)  UL 181
Fungi Resistance   No Growth  ASTM C1338
Bacteria Resistance   Meet Requirement (Anti-Bacteria)  ASTM E 2180
Corrosion of Copper/ Stainless Steel Non Corrosive DIN 1988
Nitrosamine Contents Not Detected FDA CPG 7117.11
RoHS Not Detected EN Restriction of the Use of Hazardous Substances Directive (RoHS) 2002/95/EC
Sound Reduction (       AF)
32 dB (20 mm) DIN EN ISO10052, DIN 4109-11
Flexibility Excellent ASTM C 534

Specifications comply with ASTM C534-88.

* Figures show the average values obtained by the world well-known testing institutes.

** Tested according to DIN, JIS, ASTM and others.

*** Average density of insulation thickness over 20 mm.

**** At temp. under -57 °C AEROFLEX becomes hard, but it does not affect thermal conductivity nor water vapor permeability. In the heating applications AEROFLEX can stand +125 °C continuously, and the adhesive up to +100 °C.

***** Water vapor permeability tests were done under test method ASTM E96 dehydrate test method at 37.8 °C.

****** IMO : International Maritime Organization

******* It is reported that Nitrosamin is harmful to human health even during storage. No Nitrosamin compound was detected in AEROFLEX.

 

 
 
 

 

© 2000 Eastern Polymer Group. All rights reserved.
Eastern Polymer Industry Co,. LTD.
770 Moo 6 Teperak Road, Amphure Muang, Samutprakan 10270, Thailand.
Tel:(662) 383-6599 (15 lines) Fax:(662) 383-6533,

 


 
. . . . . .